Basic Hydraulics
- System Head Curves
System curves are performance curves of piping systems. They are
graphical representations of the energy required to move a given
flow rate through a piping system and are used to identify some
of the necessary characteristics of the system's pump. The required
energy is plotted on the vertical axis and is given in terms of
head. The capacity is plotted along the horizontal axis and is given
in cubic meters per hour or liters per second. System curves are
the sum of the static suction and discharge heads and the friction
head losses of the piping system. Normally, the static heads of
a system remain fairly constant and are independent of capacity,
but friction head losses increase approximately as the square of
the velocity of the liquid passing through the system. The friction
head losses give system curves an upward curving shape as the capacity
increases.
 |
 |
|
|
|
Figure 2.4-1 shows examples of two system curves. In this figure,
the system curves for two different piping systems have been plotted
on the same graph. In system "A", there is a static head
of 10 meters and a pipeline consisting of 800 meters of 200 mm pipe.
The friction losses at various capacities have been calculated and
plotted on this graph and these points have been connected to form
a smooth curve. In system "B", the static head has been
reduced to 5 meters and the system contains 800 meters of 250 mm
pipe. The friction losses at various capacities have been plotted
for this system and connected with a smooth curve. Because the velocity
is lower in the 250 mm pipe for a given capacity, the friction losses
are less and system curve "B" has a more gradual rise
than curve "A".
Figure 2.4-1 can be used to compare system A with system B and
such comparisons are done by piping designers to determine the most
economical system layout. If a capacity of 80 liters per second
is selected, the curve for system "A" shows that 40 meters
of head will be required to deliver this flow. If system "B" is
selected, only 15 meters of head is required to deliver the same
capacity. System "B" results in a pump that runs at a
lower speed, uses less power, and will cost less to operate. However,
this reduction in operating expense may be more than offset by the
increased capital expense of the larger, more costly pipeline. The
larger pipe of system "B" may also result in a pipeline
velocity that is too low to keep the solids in the slurry in suspension.
A given system may have more than one system curve. This typically
results from a change in static head as the pump operates through
a normal cycle. An example would be a pump transferring a liquid
from one location to another. As the pump empties the suction supply
sump or tank, the liquid level will drop resulting in an increase
in the system static head. This causes the system curve to shift
upward by the amount of the increase in static head. If the pump
runs at a constant speed, the shift in the system curve will make
the pump deliver less flow at the higher system head. Figure 2.4-2
has a pump performance curve plotted with the system curves and
shows the change in flow resulting from a change in the static system
head. The amount of change in flow depends on the shape of the system
curve and how much the static head has increased. Because slurry
pumps usually have fairly flat performance curves, even small changes
in the static system head can make significant changes to the flow
rate.
Pumps always operate at the point where the system curve intersects
the pump performance curve. This graphic intersection represents
the capacity where the energy required to move the liquid through
the piping system equals the energy transferred to the liquid by
the pump. In the example given above, the pump will deliver capacity "H" when
the suction sump level is high and capacity "L" when the
sump level is low. When there is a change in the static head of
a system during normal operation, it is necessary to plot system
curves for the high and low levels and determine if the selected
pump will deliver a suitable range of flows.
The calculation of the system curve is usually the responsibility
of the system designer or purchaser of a pump. Many factors are
involved in determining the system curve, and the details of the
process are well covered in handbooks common in the pump industry.
A number of the variables in this process are selected from a range
of possible values which makes the process subject to some interpretation.
If the selected friction factor is higher than what is actually
encountered in the system, the system will have a calculated system
curve and an actual system curve as shown in Figure 2.4-3. The higher
friction factor chosen results in a system curve that is steeper
than the actual curve which may cause problems.
 |
 |
|
|
|
Figure 2.4-3 shows a pump performance curve intersected by two
system curves, the calculated curve "C" and the actual
curve "A". The pump and system are expected to operate
at capacity "S" but will actually deliver capacity "R".
In systems that pump non-abrasive liquids, control valves are installed
in the discharge line to adjust for differences between the calculated
and actual system curves. However, when abrasives are being handled,
control valves are seldom used because of the high wear rate. Unless
the pump is equipped with a means of regulating its speed, it will
operate at the higher capacity. This may allow the pump to periodically
drain the sump if the capacity is greater than the filling rate
of the sump. This results in surging that will sharply decrease
the pump's wear life and can damage other system components. It
may also have adverse effects on the process being performed by
the system.
Figure 2.4-4 is a graph of what happens when a pump is surging.
The graph is plotted from test data of a surging pump and has capacity
plotted on the vertical axis and time plotted on the horizontal
axis. The pump starts out delivering 90 liters per second, and as
the sump level drops to a point where the suction inlet is exposed,
the flow rate rapidly decreases. The pump operates at this reduced
flow rate until the sump level fills to the point the suction inlet
is fully submerged and the flow increases to nearly the original
value. The cycle repeats as the sump is again emptied faster than
it is replenished.
There are other problems associated with pumping at a capacity
greater than the design point. The increased flow rate will result
in the pump drawing more power than expected which may overload
the motor. Increased capacities will require a higher net positive
suction head, and if it is not available, the pump will cavitate.
The pump could also wear out faster than anticipated because of
the increased internal velocities caused by the greater volume being
handled. For these reasons, it is always good practice to allow
for safe operation of the system at capacities slightly higher than
the design flow.
Back To Technical References
|